How Jet Fan Calculator counts jet fans
For each fire location, the app adds the pressure losses the airflow must overcome, multiplies the total by the cross section to get the thrust needed, and divides by the useful thrust of one fan. It repeats this every 10 m and once 0.1 m before the exit; the required number is the largest count.
The fire-location sweep
The fire location xf is measured from the entrance, the way the air flows. The app places the fire at 0, 10, 20 m and so on while xf ≤ L, then once at L − 0.1 m. Each location is a table row; the required number is the largest row, never below zero.
A row can show a negative count when an assisting slope or meteorological pressure outweighs the losses at that location. Fires between the sweep points are not evaluated.
Air, tunnel and fire temperatures
The app works out the ambient air density from temperature and altitude, the hydraulic diameter from cross section and perimeter, and the maximum temperature with the fire's convective heat fully mixed into the airflow. The design velocity is the critical air velocity you enter. Downstream of the fire, the temperature decays over a characteristic length.
- ρ = 352.98 / (T + 273.15) · e(−h / 8435)Ambient air density, from ambient temperature T and tunnel altitude h
- Dh = 4 · A / PHydraulic diameter, from cross section A and perimeter P
- V = VcDesign velocity equals the critical air velocity you enter
- Tmax = T + χ · Q · 106 / (ρ · 1005 · V · A)Maximum temperature, full mixing, cp = 1005 J/(kg·K)
- xe = 18.5 · (Q · 106)1/3Characteristic length of the downstream decay
- Td = T + (1 − e(−(L − xf) / xe)) · (Tmax − T) · xe / (L − xf)Average temperature downstream of the fire (the table's temperature column); at the exit the app uses Tmax
- ρd = ρ · (T + 273.15) / (Td + 273.15); Vd = (ρ / ρd) · VDensity and air velocity downstream of the fire
The pressure losses
At each fire location the app adds ten terms: the entrance and exit losses, wall friction before and after the fire, adverse wind, drag from cars, LCVs and HGVs between the entrance and the fire, fire buoyancy on a slope, fire blockage, and the meteorological pressure you enter. Their sum times the cross section is the thrust needed.
| Term | Formula | Depends on |
|---|---|---|
| Entrance | Δpin = ξin · ½ρV² | Entrance loss coefficient, ambient density, design velocity |
| Exit | Δpout = ξout · ½ρdVd² | Exit loss coefficient, downstream density and velocity |
| Wall friction | Δpf = ½ρV² · λ · xf / Dh + ½ρdVd² · λ · (L − xf) / Dh | Friction factor, length before and after the fire |
| Adverse wind | Δpw = ½ρvw² | Adverse wind speed |
| Vehicles | Δpv = Σ ½ρV² · Cd · (Av / A) · (xf / 1000) · Nclass · n | Cars, LCVs and HGVs between the entrance and the fire, at the design velocity; Nclass = traffic density × share / (PCU factor × 100) |
| Fire buoyancy | Δpb = (ρ − ρd) · g · (L − xf) · (−s) / 100 | Slope over the hot section downstream of the fire |
| Fire blockage | Δpfb = 9×10−5 · χ · Q · 106 / (Dh² · V) | Convective heat, hydraulic diameter, design velocity |
| Meteorological | pmet | Added as entered, with its sign |
- Δp = Δpin + Δpout + Δpf + Δpw + Δpv + Δpb + Δpfb + pmetTotal pressure loss for this fire location
- F = Δp · AThrust the jet fans must supply
Useful thrust of one fan
The app reduces the bench thrust you enter by a velocity factor from the fan and hydraulic diameters, by your installation factor, and by the ratio of the average tunnel air density to the fan test density. The thrust needed divided by that useful thrust, rounded up, is the count for one fire location.
- kv = 1 − 1.2 · (Df / Dh)²Fan velocity factor. A fan too large for the tunnel (kv ≤ 0) is refused at the fan-diameter field
- Tavg = (T · xf + Td · (L − xf)) / L; ρavg = ρ · (T + 273.15) / (Tavg + 273.15)Average temperature and air density over the whole tunnel
- N = F / (Fb · kv · ki · ρavg / ρtest), rounded upJet fans for this fire location, rounded up to a whole fan
The default inputs
With the app's defaults (a 20 MW fire in a 1,100 m level tunnel of 92 m², 3 m/s critical velocity, 1,020 N fans of 1.25 m), a fire at the entrance needs 5 fans and a fire at the exit needs 6. From 470 m on every row needs 6, so the required number is 6.
| Value | Fire at 0 m | Fire at 1100 m |
|---|---|---|
| Average temperature downstream | 76.49 °C | 81.20 °C |
| Total pressure loss | 29.67 Pa | 45.82 Pa |
| Thrust | 2730 N | 4216 N |
| Jet fans | 5 | 6 |
The derived values on the results screen: air density 1.0924 kg/m³, hydraulic diameter 9.20 m, design velocity 3.00 m/s, maximum temperature 81.20 °C. The table has 112 rows: 0 to 1100 m, then 1099.9 m.
Inputs and limits
The calculation is simplified, and several inputs change the count a lot. Read these before you rely on a result, and compare the method with the one that governs your project. Figures are the engine's output for the default inputs with one value changed. A qualified engineer must verify every result.
- Critical velocity is an input, not calculated. The app uses the value you enter as the design velocity and does not work it out from the fire or the tunnel. The count is very sensitive to it: 3 m/s gives 6 fans, 4 m/s gives 10 and 6 m/s gives 21.
- No spare or fire-zone fans. The count is the thrust needed divided by one fan's useful thrust, rounded up, with nothing added: no redundancy for maintenance and no allowance for fans in the fire zone that may stop working. Add any allowance your design method requires.
- A simple fan thrust model. Bench thrust is reduced only by the velocity factor 1 − 1.2 (Df/Dh)², your installation factor and the air density ratio. There is no correction for tunnel air velocity against jet velocity (fan velocity is reference only), no fan spacing, position or wall-proximity model beyond the factor you enter, and the fan's temperature rating is not checked against the smoke temperature.
- Fan spacing is not used. A minimum spacing of 25 fan diameters is computed internally, but it is not shown on the results screen and does not enter the count.
- One-dimensional, steady and swept in steps. The fire is placed at 0, 10, 20 m and so on and once 0.1 m before the exit; fires between those points are not evaluated. Air flows from the entrance to the exit.
- Fire model constants come from the original calculation. The maximum temperature assumes full mixing with cp 1005 J/(kg·K); the downstream decay length is 18.5 × (Q·106)1/3; fire blockage is 9×10−5 χ Q·106 / (Dh² V). The app does not cite a source for them.
- Traffic drag is simplified. Only vehicles between the entrance and the fire add drag, at the design air velocity (the vehicles' own speed is not modelled), from traffic density × share ÷ PCU factor per lane × lanes. Car, LCV and HGV shares that don't add up to 100 % only bring a note; the values are used as entered.
- Wind and meteorological pressure. Adverse wind adds ½ρvw². Meteorological pressure is added to the total as entered, with its sign: −500 Pa makes every row negative and the required number 0.
- Slope enters only fire buoyancy, over the hot section downstream of the fire, with −s: a positive slope lowers the loss and a negative slope raises it. The app does not state which way along the tunnel a positive slope rises. −3 % gives 11 fans; +3 % gives 6, the same as level.
- Rows can be negative. An assisting slope or pressure can give a negative count for a row (+3 % slope: −1 fans with the fire at the entrance). The required number is never below 0.
- Five fields are not used. Height, width, fan velocity, temperature resistance and power consumption are recorded but change nothing in the result.
- Input ranges are the app's own assumptions, not limits of real tunnels: for example length above 0 up to 20,000 m, slope −15 to 15 %, heat release rate 0 to 500 MW, bench thrust 1 to 20,000 N, and 1 to 10 whole lanes.
- No named standard, SI units only. The app implements no named standard and claims no compliance with one. There is no unit switch, and numbers use a dot as the decimal mark whatever your phone's language.