You enter the fire, the space or the stair's leakage paths, and the app applies published NFPA 92 and Handbook of Smoke Control Engineering equations on the phone. The engine is a separate module; the screens and exports show its steps and never re-implement its math. Figures below are the engine's output for the app's default inputs.

Atrium smoke control · Step 1

Convective heat and flame height

The app takes the convective part of your fire, Qc = χc · Q (NFPA 92 Eq. 5.5.1.3, χc 0.7 by default), and the limiting flame height zl = 0.166 · Qc2/5 (Eq. 5.5.1.1d). For the default 5,000 kW fire that is 3,500 kW of convective heat and a 4.34 m flame.

  • Qc = χc · QNFPA 92 Eq. 5.5.1.3
  • zl = 0.166 · Qc2/5NFPA 92 Eq. 5.5.1.1d
Atrium smoke control · Step 2

Plume mass flow

Above the flame (z > zl) the app uses m = 0.071 · Qc1/3 · z5/3 + 0.0018 · Qc (Eq. 5.5.1.1e); at or within it, m = 0.032 · Qc3/5 · z (Eq. 5.5.1.1f). The default 10 m clear height gives 56.34 kg/s. If the plume would be under 2.2 °C above ambient, it gives no result.

  • m = 0.071 · Qc1/3 · z5/3 + 0.0018 · QcNFPA 92 Eq. 5.5.1.1e, interface above the flame (z > zl)
  • m = 0.032 · Qc3/5 · zNFPA 92 Eq. 5.5.1.1f, interface at or within the flame (z ≤ zl)

The two equations do not meet at the flame height: for the default fire, 18.59 kg/s at z = zl and 18.76 kg/s just above it.

Atrium smoke control · Step 3

Smoke layer temperature, density and exhaust

The layer temperature is Ts = T0 + Ks · Qc / (m · cp) (Eq. 5.5.5), the density ρs = Patm / (287 · Ts,abs) (Eq. 5.8b), and the required exhaust V = m / ρs (Eq. 5.7b). Defaults give 82.13 °C, 0.9937 kg/m³ and 56.69 m³/s, with the exhaust mass flow equal to the plume mass flow.

  • Ts = T0 + Ks · Qc / (m · cp)NFPA 92 Eq. 5.5.5
  • ρs = Patm / (287 · (Ts + 273.15))NFPA 92 Eq. 5.8b; NFPA prints +273, about 0.05 % different in density
  • V = m / ρsNFPA 92 Eq. 5.7b

Keep Ks at 1.0 when you size the exhaust. The app accepts any value above 0 and up to 1 without a warning, and a lower one gives a smaller exhaust: 51.73 m³/s at 0.5 instead of 56.69 m³/s (−8.7 %). NFPA 92 5.5.5.1 uses 1.0 for exhaust sizing unless test data or an engineering analysis supports another value.

Atrium smoke control · Step 4

Smoke filling with no exhaust

With no exhaust and a steady fire, the app uses NFPA 92 Eq. 5.4.2.1b for the height of the first indication of smoke at your chosen time, and solves it for the time to reach your clear height. Defaults: first indication at 10.87 m after 60 s; smoke reaches the 10 m clear height after 70.1 s.

  • z/H = 1.11 − 0.28 · ln[(t · Q1/3 · H−4/3) / (A/H²)]NFPA 92 Eq. 5.4.2.1b, for 0.9 ≤ A/H² ≤ 14 and z/H > 0.2
  • t = (A/H²) · H4/3 · Q−1/3 · exp[(1.11 − z/H) / 0.28]The same equation solved for the time to reach the design clear height

It applies only for A/H² from 0.9 to 14 and z/H above 0.2, in a space with a uniform cross-section; outside that, the plume and exhaust results still stand and the estimate is withheld. A z/H above 1 means the layer has not started to descend. If the time you choose is too late for the equation, the time to reach your clear height is hidden too; pick an earlier time and it appears.

Stairwell pressurization · Step 5

Leakage inventory and supply airflow

Each leakage path is n × area, or n × leakage ratio × wall or floor area, using NFPA 92 Table A.4.4.4.3 typical ratios or your own. All paths are summed in parallel and the supply is Q = C · Ae · √(2ΔP/ρ). The default inventory, 0.266 m² at 25 Pa with C 0.65, needs 1.116 m³/s.

  • Ai = n · a or Ai = n · r · SDirect area, or area ratio × surface area
  • Ae = Σ AiAll paths in parallel (Handbook of Smoke Control Engineering)
  • Q = C · Ae · √(2 · ΔP / ρ)With C 0.65 and ρ 1.2 kg/m³ this is Q = 0.839 · Ae · √ΔP

One pressure difference applies to every path: the app models no stack effect, wind, building HVAC or series paths, and doors and other openings need your own leakage areas.

Typical leakage area ratios the app offers (m² per m², NFPA 92 Table A.4.4.4.3)
PathTightAverageLooseVery loose
Stairwell wall0.14 × 10⁻⁴0.11 × 10⁻³0.35 × 10⁻³None
Exterior wall0.50 × 10⁻⁴0.17 × 10⁻³0.35 × 10⁻³0.12 × 10⁻²
Elevator shaft wall0.18 × 10⁻³0.84 × 10⁻³0.18 × 10⁻²None
Floor0.66 × 10⁻⁵0.52 × 10⁻⁴0.17 × 10⁻³None
Stairwell pressurization · Step 6

Open-door velocity

The average velocity through an open stair door is v = Q / Ad, assuming all of the supply leaves through that one door. With the default supply, 1.116 m³/s through a 1.94 m² door gives 0.576 m/s. Supply sized for the closed-door case is usually not enough, so enter your open-door supply; the app compares with your own criterion.

  • v = Qs / AdAll supply through one open door; other paths ignored

The 1.0 m/s minimum velocity is a placeholder. Until you enter and confirm your own criterion, the check shows Set criterion instead of pass or fail.

Stairwell pressurization · Step 7

Door-opening force

For a side-hinged door with a knob, F = Fr + W · A · ΔP / (2 · (W − d)) (NFPA 92 Eq. A.4.4.2.2b). A 0.91 × 2.13 m door at 25 Pa with a 45 N closer needs 71.44 N; at 87 Pa, 137.00 N, over the commonly cited 133 N limit you can change.

  • F = Fr + W · A · ΔP / (2 · (W − d))NFPA 92 Eq. A.4.4.2.2b; d is the knob's distance from the knob-side edge
Door-opening force for the default 0.91 × 2.13 m door, 45 N closer, 133 N limit (engine output)
Pressure differenceForceCheck
25 Pa71.44 NPass
50 Pa97.87 NPass
87 Pa137.00 NFail
150 Pa203.62 NFail
Worked examples

Two cases checked against the engine

Two cases, both run through the engine. The atrium case takes its inputs from the NFPA 92 annex atrium example; the stair case is one of the engine's own test cases, which fails the door-force check. Each figure below is the engine's output. The worked examples in the app's Library are fictional projects.

Atrium, NFPA 92 annex example inputs

5,275 kW fire, 36.6 m ceiling, A/H² 1.4, 30.5 m clear height, 27 s: zl 4.44 m (the annex prints 4.43 m), m 333.38 kg/s, Ts 31.08 °C, V 287.28 m³/s, and smoke reaches 30.5 m after 26.3 s.

The annex prints a volumetric exhaust of about 278 m³/s because it assumes a density of 1.2 kg/m³. The app uses the density at the layer temperature (1.1605 kg/m³), so its 287.28 m³/s is not the annex's figure.

Stair, engine test case

20 doors × 0.025 m², 1,200 m² of loose stairwell wall and one 0.00104 m² path at 75 Pa, with a 90 N closer: Ae 0.921 m², supply 6.69 m³/s, 3.45 m/s at the door, and a door-opening force of 169.31 N, which fails against 133 N.

Read before relying on a result

Inputs and limits

Every method in the app has conditions of use, and some inputs change the result in ways the app does not warn about. Read these before you rely on a result, and check each one against the building, the system and the code edition that govern your project. Figures are engine output.

  1. Axisymmetric plume, steady fire only. No balcony spill, window, wall or corner plume; no growing (t-squared) fire; no plugholing, make-up air velocity or sprinkler interaction check.
  2. The 2.2 °C rule. When the plume would be less than 2.2 °C above ambient (NFPA 92 5.5.1.2), the app gives no result. A 50 kW fire under a 20 m ceiling with a 19 m clear height: “The plume would be only 1.112 °C above ambient; the plume equations do not apply below a 2.2 °C rise.”
  3. Smoke filling only inside its range. The estimate needs A/H² from 0.9 to 14 and z/H above 0.2, a space with a uniform cross-section with height (the app can't check that), a steady fire and no exhaust. Outside it, the plume and exhaust results still stand and the estimate is withheld: the default atrium with a 100 m² floor (A/H² 0.25) still gives 56.69 m³/s, with no estimate.
  4. First indication of smoke, not the layer interface. The descent equation gives the height of the first indication of smoke, which sits above the interface. A z/H above 1 means the layer has not started to descend, and the app shows the height at the ceiling: 1,000 kW under a 30 m ceiling over 2,000 m² at 5 s shows 30 m.
  5. A late time hides the time to the clear height too. If the time you choose gives z/H of 0.2 or less, the whole estimate is withheld, including the time for smoke to reach your clear height, which does not depend on that time. The default atrium at 300 s gives “z/H = 0.09297, outside its range … Choose an earlier time”, and the 70.1 s is not shown on the result card or in the PDF or CSV export. Choose an earlier time and it appears.
  6. Ks below 1.0 lowers the exhaust, with no warning. The app accepts any Ks above 0 and up to 1. A lower Ks gives a cooler, denser layer and a smaller required exhaust: the default 56.69 m³/s becomes 51.73 m³/s at 0.5 (−8.7 %) and 46.88 m³/s at 0.01 (−17.3 %). NFPA 92 5.5.5.1 uses 1.0 for exhaust sizing unless test data or an engineering analysis supports another value.
  7. The plume regime switches at the flame height. At z = zl the app uses the within-flame equation, and the two published equations do not meet there: for the default fire, 18.59 kg/s at zl and 18.76 kg/s just above it.
  8. Kelvin with +273.15. The density step converts with +273.15; NFPA prints +273, a difference of about 0.05 % in density.
  9. One pressure difference for the whole stair, all paths in parallel. No stack effect, wind, building HVAC, series paths (stair to floor to outside) or pressure that changes with height. Every path is a direct path between the stair and the building at your design pressure difference.
  10. Door velocity assumes all supply leaves through one open door. Other paths are ignored. Supply sized for the closed-door case is usually not enough. The 1.0 m/s minimum is a placeholder: the app shows SET CRITERION until you confirm your own criterion.
  11. Door force: one door hinged on one side, with knob hardware. The 133 N limit is the commonly cited NFPA 101 value and an input you can change.
  12. Input bands are sanity guards, not standard values. Pressure difference 5–150 Pa, air density 0.5–2.0 kg/m³, fire size up to 1,000,000 kW, ceiling height up to 1,000 m, ambient −60 to 60 °C, atmospheric pressure 50,000–120,000 Pa.
  13. Typical leakage ratios for walls and floors only. They come from NFPA 92 Table A.4.4.4.3 (below). Closed doors and other paths have no default: you enter their leakage area.
  14. SI units only. There is no cfm, lbf or inches of water input; convert first.
  15. Published examples cover only part of the method. The engine's tests compare the limiting flame height, plume mass flow and smoke-filling time with the NFPA 92 annex atrium example, and the door-opening force with two published door-force examples. No published example covers the stair supply airflow; it is compared only with a second, independent calculation of the same equations.
  16. No edition conformance. Equation numbers are as commonly cited for NFPA 92; check them against the edition your project uses.
  17. A calculation aid. Results must be reviewed by a qualified engineer. Pass and fail compare your values with the limits you enter; they are not a compliance determination.
Sources

Where the equations come from

NFPA 92 SI equations 5.5.1.3, 5.5.1.1d, 5.5.1.1e, 5.5.1.1f, 5.5.5, 5.8b, 5.7b, 5.4.2.1b and A.4.4.2.2b, and Table A.4.4.4.3; the Handbook of Smoke Control Engineering (Klote, Milke and others) for flow through leakage paths and paths in parallel. Equation numbers are as commonly cited; no edition conformance is claimed.