How HVAC Load Calculator works
HVAC Load Calculator applies the CLTD/SCL/CLF hand method from the 1997 ASHRAE Handbook of Fundamentals: conduction through walls, roofs and glass uses a cooling load temperature difference, sun through glass a solar cooling load, and people, lights and equipment a cooling load factor, hour by hour. Heating is a steady-state design load.
This build calculates with placeholder tables, not published data, so this page shows equations only, never a result. See inputs and limits.
The CLTD/SCL/CLF method
The method is the CLTD/SCL/CLF procedure of the ASHRAE Handbook of Fundamentals (1997, chapter 28) and Spitler, McQuiston and Lindsey (ASHRAE Transactions, 1993), cited as the source of the method, not as an endorsement. It is a 1990s hand-calculation simplification, valid only for the tabulated constructions, latitudes and design month.
Each wall, window and door faces one of eight compass points. Building rotation turns every face clockwise and snaps it to the nearest point. In the southern hemisphere north and south faces swap (north-east with south-east, north-west with south-west); east and west stay. Roofs are horizontal and have no direction.
Cooling, component by component
The app works out each component's load for every hour of the design day, using SI units: U in W/m²·K, areas in m², temperatures in °C, airflow in L/s. These are the equations as the app's Formulas and sources screen lists them, where every line's table values and their source are shown too.
-
Walls, doors and roofs
Q = U × A × CLTDcCLTDc = (CLTD + LM) × K + (25.5 − Tr) + (Tom − 29.4)Tom = To − range/2CLTD by wall group and compass direction (roofs by roof type), LM the latitude-month correction, K the surface-colour factor, Tr the room temperature, To the outdoor design temperature. A is net of windows and doors. -
Glass conduction
Q = U × A × CLTDcCLTDc = CLTD_glass + (25.5 − Tr) + (Tom − 29.4)The glass CLTD has no direction; the glazing library gives U and the shading coefficient. -
Sun through glass
Q = A × SC × SCLSCL by direction, hour, latitude and zone type (light, medium or heavy). SC is the glazing shading coefficient times the interior-shading factor; an exterior shade factor multiplies the result. -
Partitions and floors
Q = U × A × (T_adjoining − T_room)Steady over the day, with no hourly shape. A neighbouring space cooler than the room is a credit in cooling. -
People
Qs = N × SHG × CLF, Ql = N × LHGSensible and latent gain per person for the chosen activity. CLF depends on hours occupied, zone type and floor covering; latent has no lag. -
Lighting
Q = W × usage × special allowance × CLFHours of operation and zone type select the CLF; hours count from the first occupied hour. -
Equipment
Qs = Σ (W × CLF), Ql = Σ latentEach item has watts, a latent part and its own hours of operation. -
Infiltration and ventilation
Qs = 1.23 × L/s × ΔT, Ql = 3010 × L/s × ΔWVbz = Rp × Pz + Ra × AzVentilation is the space-type breathing-zone rate, or a direct L/s. Infiltration is air changes per hour × room volume ÷ 3.6, or a direct L/s. ΔW is the humidity-ratio difference in kg of water per kg of dry air; a drier outdoor state gives no latent credit. -
Psychrometrics
W = 0.621945 × pw / (p − pw)p = 101.325 × (1 − 2.25577e-5 × z)^5.2559 kPaSaturation pressure follows the Hyland-Wexler equations; pw is the relative humidity times the saturation pressure, and z the site elevation in metres.
The peak and the totals
The app adds the components for each of the 24 hours of the design day, in solar time, and marks the hour with the highest total. For a project, the block load is the peak of the summed hourly loads, shown beside the sum of room peaks. Your safety and fan-and-duct allowances then multiply the peak.
-
Block load and allowances
Block load = max over hours of Σ room loadsWith allowances = peak × (1 + safety) × (1 + fan and duct) -
Supply airflow
L/s = sensible load ÷ (1.23 × supply ΔT) -
Units
1 TR = 3516.85 W = 12 000 Btu/hThe engine calculates in SI. Choosing IP units changes the display and the units you type in, not the calculation.
The heating design load
Heating is a steady-state design load: conduction through every element plus the outdoor air, at the indoor and outdoor heating design temperatures, then multiplied by your safety factor. It takes no credit for people, lights, equipment or sun, and a neighbouring space warmer than the room counts as zero, not as a gain.
-
Heating
Q = Σ U × A × (Ti − To) + 1.23 × L/s × (Ti − To)Design load = Q × (1 + safety)
Inputs and limits
The app computes only what its tables cover. In this build every table is a placeholder, so results are demonstration numbers. It calculates for one design month, July north of the equator or January south of it, and latitudes from 24° to 48°; outside these it refuses to calculate rather than guess.
- Demonstration numbers. All 15 tables the engine reads (constructions, glazing, cooling load temperature differences, solar cooling loads, cooling load factors, heat gains and ventilation rates) are placeholders, not published data. Every result screen and PDF page says "Demonstration numbers"; do not use the results for design.
- One design month. July in the northern hemisphere; January in the southern, using the July tables with directions mirrored. Any other month is refused at its field with the reason.
- Latitudes 24° to 48°, north or south. Between table latitudes the app interpolates linearly; outside the range it refuses to calculate and says why at the latitude field.
- A small library: nine constructions (light frame wall, masonry cavity wall, heavy concrete wall, light insulated roof, medium roof, concrete roof, solid door, interior partition, floor to an unconditioned space), three glazings (single clear, double clear, double low-e), four people activities, four equipment presets plus a custom item, and four ventilation space types (office, classroom, residential, retail). Their values are placeholders.
- Eight compass points. Building rotation snaps each face to the nearest point; roofs are horizontal.
- Cooling needs a cooler room. A room whose indoor temperature is not below the outdoor design temperature gets no cooling result; its load is left out of the project totals and a note says so.
- Partitions and floors are steady: U × A × the temperature difference, with no hourly shape.
- Heating is steady-state, with no credit for people, lights, equipment or sun.
- Standard air at sea level. The air constants 1.23 and 3010 are for standard air; site elevation enters only through the pressure used for the humidity ratio.
- Solar time. The peak hour is in solar time, hours 1 to 24, not clock time.
- A hand method. CLTD/SCL/CLF is a 1990s hand-calculation simplification and is only valid for the tabulated constructions, latitudes and design month.
- Not implemented. It does not use the Radiant Time Series or heat-balance methods of current ASHRAE handbooks, ACCA Manual J, S or D, or EN 12831, and it does not design ducts or count duct gains, estimate annual energy, select equipment or check code compliance.
A calculation aid: verify results with a qualified engineer. See the terms for this app.
Sources the app cites
- ASHRAE Handbook of Fundamentals, 1997, chapter 28: the CLTD/SCL/CLF method.
- Spitler, McQuiston and Lindsey, ASHRAE Transactions 99(1), 1993: the CLTD/SCL/CLF procedure.
- Hyland and Wexler saturation pressure equations, as given in ASHRAE Fundamentals, chapter 1.
Sources are cited for the method only. The table values in this build are not taken from them.